Field View task report – cavity fire barriers (sample)

✓Construction QA

Field View Task Report

Cavity fire barriers · East elevation · masonry package
QA-TR-07
Exported: 06 Mar 2026
Issue 1
SAMPLE REPORT · Fictional project, names, dates and results for illustration only · structure based on real Field View task exports

1. Report scope

ProjectResidential block, 6 storeys, brick outer leaf on SFS (fictional)
Field View locationProject › QA › 01 – Brickwork › Drawings › Elevations – East › Cavity fire barriers
PackageExternal masonry & cavity fire barriers
Issued to[Brickwork subcontractor]
Issued by[Main contractor] · QA set-up and inspections by Inspector (Construction QA)
RequirementHorizontal cavity barriers at every floor slab (EI 120) and vertical barriers on compartment lines (EI 60), installed to the manufacturer’s tested detail and the project fire strategy
FilterAll tasks pinned on this drawing · task type “QA hold point”

2. Drawing with pinned tasks

L5L4L3L2L1 1 2 3 4 5 6 7 8
Signed offWork completed – awaiting QA inspectionOpened / rejected– – horizontal barrier EI 120– – vertical barrier EI 60

In Field View each pin is a task placed on the elevation drawing. The subcontractor opens the pin on a tablet, adds photos as the work is installed and changes the status; QA inspects and signs off or rejects. The drawing becomes a live map of what has been proven and what has not.

3. Status summary

8Tasks on drawing
5Signed off
2Awaiting inspection
1Rejected / open

4. Task register

#Task refDescriptionLocationIssued / targetPhotosStatus
1T-2468Install horizontal cavity barrier EI 120 at slab edgeL1 · bay A02 Feb / 09 Feb6Signed off
2T-2479Install horizontal cavity barrier EI 120 at slab edgeL1 · bay C02 Feb / 09 Feb4Signed off
3T-2560Install horizontal cavity barrier EI 120 at slab edgeL2 · bay E09 Feb / 16 Feb4Signed off
4T-3267Install vertical cavity barrier EI 60 on compartment lineL2–L3 · grid 309 Feb / 16 Feb4Signed off
5T-3290Install horizontal cavity barrier EI 120 at slab edgeL3 · bay B16 Feb / 23 Feb5Signed off
6T-3294Install vertical cavity barrier EI 60 on compartment lineL3–L4 · grid 623 Feb / 02 Mar3Work completed
7T-3299Install horizontal cavity barrier EI 120 at slab edgeL4 · bay D23 Feb / 02 Mar3Work completed
8T-3310Install horizontal cavity barrier EI 120 at slab edgeL5 · bay F02 Mar / 09 Mar2Rejected

5. Task detail – pin 8 (rejected)

TaskT-3310 · Install horizontal cavity barrier EI 120 at slab edge · L5 bay F
InstructionInstall to the manufacturer’s tested detail: barrier fully compressed against the inner face of the outer leaf with no gaps, fixed with the specified brackets at the stated centres, all joints butted tight and foil-taped.
Subcontractor comment“Barrier installed, tight to brick, no gaps.” · [Brickwork supervisor] · 04 Mar 08:42
QA commentRejected 05 Mar 11:15: joint between two lengths not taped (approx. 600 mm from window reveal); one bracket missing at the corner. Photograph again after rectification, before the next lift of brickwork closes the cavity.
Hold pointNo brickwork above this barrier until the task is signed off
Open cavity above window head before the next lift

04 Mar 08:40 · Open cavity before barrier check

Inspector checking insulation and barrier continuity

05 Mar 11:10 · QA inspection of joint and fixings

Brickwork inspection from scaffold

05 Mar 11:20 · Hold point: no next lift until signed off

6. Task status workflow

1 · OpenedQA issues the task on the drawing with the spec and photo requirements
2 · Work completedSubcontractor installs, uploads timestamped photos, adds a comment
3 · QA inspectionInspector checks on site or from photos at the hold point
4 · Signed offOr rejected back to Opened with a reason – the history stays in the record

7. Actions

ActionOwnerDue
Rectify pin 8 (tape joint, add missing bracket), re-photograph and set to Work completedBrickwork subcontractor06 Mar
Inspect pins 6 and 7 at the next visit, before the cavity is closedQA06 Mar
Issue the signed-off tasks (pins 1–5) as an evidence pack to the main contractorQA10 Mar
Attach the evidence pack to Application for Payment No. 6 and file it in the golden thread / Gateway 3 informationSubcontractor QS / Main contractor25 Mar
Prepared byInspector · QA (outsourced)
Reviewed by[Main contractor QA lead]
Data sourceField View task export, East elevation drawing